Abstract
Simulation analysis of the islanding tests with the rectifier circuit load is performed. The rectifier circuit load has the impacts to the harmonic voltage after the islanding operation, and reduces the frequency and fundamental voltage greater than if no rectifier circuit loads. It is probable that total harmonic voltage distortion occurs more than 2V in a balanced three-phase circuit, if the ratio of the rectifier circuit load is at least 10%. However, the changes in the harmonic voltage after the islanding operation are dependent on the difference between the harmonic voltage included in the system power supply and the harmonic voltage by the rectifier circuit load. The characteristics on the islanding detection time are clarified in case of using the new active islanding detection method that is called a frequency feedback method with step reactive power injection
چکیده
آنالیز شبیه سازی آزمایشهای جزیرهای شدن همراه با بار مداری یکسو کننده، انجام شده است. بار مداری یکسو کننده، تاثیراتی روی ولتاژ هارمونیکی بعد از عملکرد جزیرهای دارد و فرکانس و ولتاژ مولفه اصلی را، در مقایسه با حالتی که هیچ بار مداری یکسو کنندهای وجود نداشته باشد، بیشتر کاهش میدهد. این احتمال وجود دارد که اگر نسبت بار مداری یکسو کننده حداقل 10% باشد، اعوجاج هارمونیکی کلی ولتاژ بیشتر از2V، در مدار سه فاز متعادل اتفاق میافتد. اما تغییرات در ولتاژ هارمونیکی بعد از عملکرد جزیرهای، به تفاوت بین ولتاژ هارمونیکی گنجانده شده در سیستم تغذیه توان، و ولتاژ هارمونیکی ناشی از بار مداری یکسو کننده، بستگی دارد. مشخصات زمان تشخیص جزیرهای شدن، در حالت استفاده از روش تشخیص جزیرهای شدن فعال، که "روش فیدبک فرکانسی با تزریق توان راکتیو مرحلهای" نامیده میشود، روشن شده است.
1-مقدمه
زمانی که نفوذ فراروان مولدهای پراکنده، مانند سیستمهای فتوولتائیکPV، در سیستمهای توزیع افزایش پیدا بکند، برای سیستمهایPV بسیار مهم میباشد که حالت جزیرهای ناشی از خطای سیستم قدرت را به سرعت تشخیص دهد تا ایمنی الکتریکی را تضمین بکند...